Skip to main navigation Skip to search Skip to main content

Comparative Study of Seismic Performance of SLB, TADAS and Viscous Fluid Energy Dissipators in Hospitals

  • Universidad Peruana de Ciencias Aplicadas
  • Universitat Politècnica de Catalunya (UPC)

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

Abstract

Structural damage not only causes material losses but also human losses, especially in the case of essential buildings such as health facilities, as they must ensure the provision of medical services during and after an earthquake. On the other hand, Peru is a highly seismic country due to its location on the western edge of South America, an area where the Nazca and South American tectonic plates converge. For this reason, it is essential to reinforce these infrastructures with devices that help prevent and reduce damage caused by earthquakes and guarantee the safety of the hospital. This paper studies the seismic performance of three energy dissipators: Shear Link Bozzo (SLB), Triangular Plate Added Damping and Stiffness (TADAS) and viscous fluid; incorporated into an existing hospital in Peru. The methodology involves modeling these three devices using ETABS software and evaluating the following study cases: (i) without energy dissipators, (ii) with the three seismic devices evaluated separately. Non-linear time-history analysis is conducted, considering seven seismic records compatible with the response spectrum constructed from the parameters of the Peruvian Standard E.030. Finally, it was concluded that the viscous fluid dissipator is the best option to implement in the hospital since the maximum drifts, accelerations and shear forces on each floor were reduced by 45, 23 and 27%.

Original languageEnglish
Title of host publicationProceedings of the 4th International Civil Engineering and Architecture Conference - CEAC 2024
EditorsMarco Casini
PublisherSpringer Science and Business Media Deutschland GmbH
Pages347-357
Number of pages11
ISBN (Print)9789819754762
DOIs
StatePublished - 2025
Event4th International Civil Engineering and Architecture Conference, CEAC 2024 - Seoul, Korea, Republic of
Duration: 15 Mar 202417 Mar 2024

Publication series

NameLecture Notes in Civil Engineering
Volume534 LNCE
ISSN (Print)2366-2557
ISSN (Electronic)2366-2565

Conference

Conference4th International Civil Engineering and Architecture Conference, CEAC 2024
Country/TerritoryKorea, Republic of
CitySeoul
Period15/03/2417/03/24

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 3 - Good Health and Well-being
    SDG 3 Good Health and Well-being

Keywords

  • Energy dissipators
  • Hospitals
  • Seismic performance
  • Shear Link Bozzo (SLB)
  • Triangular plate added damping and stiffness (TADAS)
  • Viscous fluid dissipators

Fingerprint